Electrical load calculator

Four different numbers get called “load” and confusing them is expensive. Connected load is everything wired in. Peak demand is what actually coincides. kVA is what generators and UPS units are rated in. And sanctioned load is what your distribution company has approved — and, where fixed charges are levied per kilowatt, what you pay for every month whether you draw it or not.

What is connected

Count everything wired in, including things you rarely use. This total is what a DISCO survey records as connected load.

Connected items, wattage and quantity
ItemWatts eachHow manyTotal WRemove
Lighting point (LED)144
Ceiling fan325
Refrigerator160
Air conditioner 1.5 ton3,600
Electric geyser2,000
Water pump 1 HP950

Typical Pakistani households run 40 to 55 per cent diversity — the summer evening peak, when the air conditioners, the fans and the lights coincide. Sites with large motors run a lower power factor; resistive loads such as geysers and heaters sit close to 1.

Load summary

3.23 kW realistic peak

  • Connected load (everything, as surveyed)7.18 kW
  • Peak demand at 45% diversity3.23 kW
  • Apparent power at PF 0.853.8 kVA
  • Current, single phase at 230 V17 A
  • Current, three phase at 400 V5 A
  • Sanctioned load to apply for4 kW
  • Supply type indicatedSingle phase is adequate

The suggested sanction adds 15 per cent headroom to the realistic peak. Sanctioning far above that costs money every month wherever fixed or demand charges are levied per kilowatt; sanctioning below it risks an unauthorised-load finding at inspection. For a generator or UPS, size on the kVA figure and allow extra for motor starting surge.

What diversity factor should I use for a Pakistani house?

Between 40 and 55 per cent for a typical household. Use the higher end if you run multiple air conditioners simultaneously through the summer evening, and the lower end if your heavy loads — geyser, pump, iron — are naturally staggered through the day.

How do I size a generator or UPS from this?

Use the kVA figure, then add headroom for motor starting surge, which can be several times running current on a refrigerator compressor or a water pump. For a UPS, also check the battery: capacity in amp-hours times battery voltage times a usable depth of discharge of about 50 per cent gives the watt-hours actually available, and that is usually the real limit rather than the inverter rating.

How do I find out my current sanctioned load?

It is on the connection agreement and in the account file at your sub-divisional office. Commercial and industrial bills print it in the header; small domestic bills frequently do not.

Does a higher sanctioned load raise my domestic bill?

On an ordinary energy-only domestic tariff you pay for units, so it does not directly. It matters wherever fixed or demand charges are levied per kilowatt, and it determines the maximum solar system size you can have approved.

A planning aid, not a design. Cable sizing, protection coordination and earthing are engineering decisions for a qualified electrician, and any application to change a sanctioned load involves a DISCO survey that supersedes this estimate. Use it to arrive at that conversation with a defensible number.